Table 17:
1 A channels: input with minimum operating down to 40 mA
Operating
voltage
TripPickup
Stabilizing
resistor R
ohms
Operating
current level
1 A
Stabilizing
resistor R
ohms
Operating
current level
1 A
20 V
500
0.040 A
--
--
40 V
1000
0.040 A
--
--
60 V
1500
0.040 A
600
0.100 A
80 V
2000
0.040 A
800
0.100 A
100 V
2500
0.040 A
1000
0.100 A
150 V
3750
0.040 A
1500
0.100 A
200 V
5000
0.040 A
2000
0.100 A
Table 18:
5 A channels: input with minimum operating down to 100 mA
Operating
voltage
TripPickup
Stabilizing
resistor R1
ohms
Operating
current level
5 A
Stabilizing
resistor R1
ohms
Operating
current level
5 A
Stabilizing
resistor R1
ohms
Operating
current level
5 A
20 V
200
0.100 A
100
0.200 A
--
--
40 V
400
0.100 A
200
0.200 A
100
0.400
60 V
600
0.100 A
300
0.200 A
150
0.400 A
80 V
800
0.100 A
400
0.200 A
200
0.400 A
100 V
1000
0.100 A
500
0.200 A
250
0.400 A
150 V
1500
0.100 A
750
0.200 A
375
0.400 A
200 V
2000
0.100 A
1000
0.200 A
500
0.400 A
The current transformer saturation voltage must be at least 2 ˣ
TripPickup
to have
sufficient operating margin. This must be checked after calculation of
TripPickup
.
When the R value has been selected and the
TripPickup
value has been set, the
sensitivity of the scheme
IP
can be calculated. The IED sensitivity is decided by the
total current in the circuit according to equation
.
(
)
IP
n IR Ires
lmag
= ×
+
+
å
EQUATION1747 V1 EN-US
(Equation 14)
where:
n
is the CT ratio
IP
primary current at IED pickup,
Table continues on next page
Section 7
1MRK 511 401-UUS A
Differential protection
132
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...