7.1.3
Connection examples for high impedance differential
protection
GUID-8C58A73D-7C2E-4BE5-AB87-B4C93FB7D62B v5
WARNING! USE EXTREME CAUTION!
Dangerously high
voltages might be present on this equipment, especially on the plate
with resistors. De-energize the primary object protected with this
equipment before connecting or disconnecting wiring or performing
any maintenance. The plate with resistors should be provided with a
protective cover, mounted in a separate box or in a locked cubicle.
National law and standards shall be followed.
7.1.3.1
Connections for three-phase high impedance differential protection
GUID-C12CCAAF-5AE5-4A9C-AC9C-F56A66FD2C14 v8
Generator, reactor or busbar differential protection is a typical application for three-
phase high impedance differential protection. Typical CT connections for three-phase
high impedance differential protection scheme are shown in figure
L1
(A)
L2
(B)
L3
(C)
Protected Object
CT 1200/1
Star/Wye
Connected
L1
(A)
L2
(B)
L3
(C)
CT 1200/1
Star/Wye
Connected
7
8
9
1
0
1
1
1
2
1
2
3
4
5
6
AI01
(I)
AI02
(I)
AI03
(I)
AI04
(I)
AI05
(I)
AI06
(I)
7
6
X1
R
4
R
5
R
6
1
2
1
2
1
2
11
12
13
14
U
U
U
R
1
1
3
4
2
1
3
R
2
2
4
1
3
R
3
2
4
1
2
3
4
5
6 7
L1 (A)
L2 (B)
L3 (C)
N
3-Ph Plate with Metrosils and Resistors
2
3
5
4
X
X
L1 (A)
L2 (B)
L3 (C)
N
1
IED
SMAI2
BLOCK
REVROT
^GRP2_A
^GRP2_B
^GRP2_C
^GRP2_N
G2AI3P
G2AI1
G2AI2
G2AI3
G2AI4
G2N
ANSI09000169-4-en.vsdx
ANSI09000169 V4 EN-US
Figure 50:
CT connections for high impedance differential protection
1MRK 511 401-UUS A
Section 7
Differential protection
Bay control REC670 2.2 ANSI
135
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...