op
2
NS
r
TD
t
I
I
=
æ
ö
ç
÷
è
ø
EQUATION1740-ANSI V1 EN-US
(Equation 96)
where:
t
op
is the operating time in seconds of the negative sequence overcurrent IED
TD
is the generator capability constant in seconds
I
NS
is the measured negative sequence current
I
r
is the generator rated current
By defining parameter x equal to maximum continuous negative sequence rating of the
generator in accordance with the following formula
7%
0.07
=
=
x
pu
EQUATION1756-ANSI V1 EN-US
(Equation 97)
Equation
can be re-written in the following way without changing the value for the
operate time of the negative sequence inverse overcurrent IED:
op
2
NS
r
2
TD
t
I
x I
1
x
×
=
×
æ
ö
ç
÷
è
ø
EQUATION1741-ANSI V1 EN-US
(Equation 98)
In order to achieve such protection functionality with one CVGAPC functions the
following must be done:
1. Connect three-phase generator currents to one CVGAPC instance (for example,
GF01)
2. Set parameter
CurrentInput
to value
NegSeq
3. Set base current value to the rated generator current in primary amperes
4. Enable one overcurrent step (for example, OC1)
5. Select parameter
CurveType_OC1
to value
Programmable
Section 11
1MRK 511 401-UUS A
Multipurpose protection
278
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...