1PT1 and 2PT1
Indicates that single-pole or two-pole auto reclosing is in progress. It is used to
temporarily block an ground-fault and/or pole disagreement function during the single-
pole or two-pole open interval.
3PT1, 3PT2, 3PT3, 3PT4 and 3PT5
Indicates that three-pole auto reclosing shots one to five are in progress. The signals
can be used as an indication of progress or for own logic.
ABORTED
The
ABORTED
output indicates that the auto recloser is inhibited while it is in one of
the following internal states:
•
inProgress: auto recloser is started and dead time is in progress
•
reclaimTimeStarted: the circuit breaker closing command has started the reclaim
timer
•
wait: an auto recloser, acting as slave, is waiting for a release from the master to
proceed with its own reclosing sequence
ACTIVE
Indicates that the auto recloser is active, from start until end of reset time.
BLOCKED
Indicates that auto recloser is temporarily or permanently blocked.
CLOSECMD
Connect to a binary output for circuit breaker closing command.
COUNT1P, COUNT2P, COUNT3P1, COUNT3P2, COUNT3P3,
COUNT3P4 and COUNT3P5
Indicates the number of auto reclosing shots made for respective shot.
COUNTAR
Indicates the total number of auto reclosing shots made.
INHIBOUT
If the
INHIBIT
input is activated it is reported on the
INHIBOUT
output.
INPROGR
Indicates that an auto recloser sequence is in progress, from start until circuit breaker
close command.
Section 14
1MRK 511 401-UUS A
Control
340
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...