1. that the busbar or load voltage is regulated to a preset target value
2. that the load is shared between parallel transformers in proportion to their ohmic
short circuit reactance
If the transformers have equal percentage impedance given in the respective
transformer MVA base, the load will be divided in direct proportion to the rated power
of the transformers when the circulating current is minimized.
This method requires extensive exchange of data between the TR8ATCC (90) function
blocks (one TR8ATCC (90) function for each transformer in the parallel group).
TR8ATCC (90) function block can either be located in the same IED, where they are
configured in PCM600 to co-operate, or in different IEDs. If the functions are located
in different IEDs they must communicate via GOOSE interbay communication on the
IEC 61850 communication protocol. Complete exchange of TR8ATCC (90) data,
analog as well as binary, via GOOSE is made cyclically every 300 ms.
The busbar voltage V
B
is measured individually for each transformer in the parallel
group by its associated TR8ATCC (90) function. These measured values will then be
exchanged between the transformers, and in each TR8ATCC (90) block, the mean
value of all V
B
values will be calculated. The resulting value V
Bmean
will then be used
in each IED instead of V
B
for the voltage regulation, thus assuring that the same value
is used by all TR8ATCC functions, and thereby avoiding that one erroneous
measurement in one transformer could upset the voltage regulation. At the same time,
supervision of the VT mismatch is also performed. This works such that, if a measured
voltage V
B
, differs from V
Bmean
with more than a preset value (setting parameter
VTmismatch
) and for more than a pre set time (setting parameter
tVTmismatch
) an
alarm signal VTALARM will be generated.
The calculated mean busbar voltage V
Bmean
is shown on the local HMI as a service
value BusVolt under
Main menu/Test/Function status/Control/
TransformerVoltageControl(ATCC,90)/TR8ATCC:x
.
Measured current values for the individual transformers must be communicated
between the participating TR8ATCC (90) functions, in order to calculate the circulating
current.
The calculated circulating current I
cc_i
for transformer “i” is shown on the HMI as a
service value ICIRCUL under
Main menu/Test/Function status/Control/
TransformerVoltageControl(ATCC,90)/TR8ATCC:x
.
When the circulating current is known, it is possible to calculate a no-load voltage for
each transformer in the parallel group. To do that the magnitude of the circulating
current in each bay, is first converted to a voltage deviation, V
di
:
Section 14
1MRK 511 401-UUS A
Control
422
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...