16.1.2.4
Lock-out
M14828-18 v5
The SMPPTRC function block is provided with possibilities to initiate lock-out. The
lock-out can be set to only activate the block closing output CLLKOUT or initiate the
block closing output and also maintain the trip signal output TR3P (latched trip).
The lock-out can then be manually reset after checking the primary fault by activating
the input reset lock-out RSTLKOUT.
If external conditions are required to initiate a closing circuit lock-out but not to
lockout trip, this can be achieved by activating input SETLKOUT. The setting
AutoLock
=
Disabled
means that the internal trip will not activate lock-out so only
initiation of the input SETLKOUT will result in lock-out. This is normally the case for
overhead line protection where most faults are transient. Unsuccessful autoreclose and
back-up zone tripping can in such cases be connected to initiate lock-out by activating
the input SETLKOUT.
16.1.2.5
Example of directional data
GUID-08AC09AB-2B2F-4095-B06E-1171CF225869 v2
An example how to connect the directional data from different application functions to
the trip function is given below, see Figure
:
1MRK 511 401-UUS A
Section 16
Logic
Bay control REC670 2.2 ANSI
489
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...