17.2.3
Setting guidelines
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v2
The parameters for Gas medium supervision SSIMG can be set via local HMI or
Protection and Control Manager PCM600.
Operation
: This is used to disable/enable the operation of gas medium supervision i.e.
Off/On.
PresAlmLimit
: This is used to set the limit for a pressure alarm condition in the circuit
breaker.
PresLOLimit
: This is used to set the limit for a pressure lockout condition in the circuit
breaker.
TempAlarmLimit
: This is used to set the limit for a temperature alarm condition in the
circuit breaker.
TempLOLimit
: This is used to set the limit for a temperature lockout condition in the
circuit breaker.
tPressureAlarm
: This is used to set the time delay for a pressure alarm indication,
given in s.
tPressureLO
: This is used to set the time delay for a pressure lockout indication, given
in s.
tTempAlarm
: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut
: This is used to set the time delay for a temperature lockout indication,
given in s.
tResetPressAlm
: This is used for the pressure alarm indication to reset after a set time
delay in s.
tResetPressLO
: This is used for the pressure lockout indication to reset after a set time
delay in s.
tResetTempLO
: This is used for the temperature lockout indication to reset after a set
time delay in s.
tResetTempAlm
: This is used for the temperature alarm indication to reset after a set
time delay in s.
1MRK 511 401-UUS A
Section 17
Monitoring
Bay control REC670 2.2 ANSI
523
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...