Three Phase Trafo
: The function considers the given transformer as three phase
transformer.
•
Single Phase Trafo
: The function considers the given transformer as single phase
transformer.
Based on the settings
TrafoRating
and
TrafoType
, transformer parameters are selected
for temperature calculations. Both IEEE and IEC standards defines the transformer
parameters based on three categories of transformer rating.
In the case of three phase transformers:
•
If the transformer rating is less than 2.5 MVA, the function considers this as a
distribution transformer.
•
If the transformer rating is less than 100 MVA, it is considered as a medium power
transformer.
•
If the transformer rating is above 100 MVA, it is considered as a larger power
transformer.
In the case of single phase transformers:
•
If the transformer rating is less than 0.833 MVA, the function considers this as a
distribution transformer.
•
If the transformer rating is less than 33.3 MVA, it is considered as a medium
power transformer.
•
If the transformer rating is above 33.3 MVA, it is considered as a larger power
transformer.
NoOfWindings
: This setting is used to set the number of windings in the transformer.
The options are :
•
Three winding
: The function considers the given transformer as three winding
transformer.
•
Two winding
: The function considers the given transformer as two winding
transformer.
Based on the setting
NoOfWindings
, hot spot temperature of the winding 3 is either
calculated or assigned as zero.
ConstSelection
: This setting is used to select the transformer parameters taken either
from IEC 60076-7 standard or IEEE C57.96-1995 standard. The options are:
1MRK 511 401-UUS A
Section 17
Monitoring
Bay control REC670 2.2 ANSI
551
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...