Table 66. Voltage control TR1ATCC/TR8ATCC , TCMYLTC/TCLYLTC , continued
Function
Range or value
Accuracy
Time after position change before the value is accepted
(1–60) s
±0.2% or ±200 ms
whichever is greater
Tap changer constant time-out
(1–120) s
±0.2% or ±200 ms
whichever is greater
Raise/lower command output pulse duration
(0.5–10.0) s
±0.2% or ±200 ms
whichever is greater