GlobalBaseSel
: It is used to select a GBASVAL function for reference of base values.
RotResU
: It is a setting for rotating the polarizing quantity (3V
0
) by 0 or 180 degrees.
This parameter is set to 180 degrees by default in order to inverse the residual voltage
(3V
0
) to calculate the reference voltage (-3V
0
e
-jRCADir
). Since the reference voltage is
used as the polarizing quantity for directionality, it is important to set this parameter
correctly.
With the setting
OpModeSel
the principle of directional function is chosen.
With
OpModeSel
set to
3I0cosfi
the current component in the direction equal to the
characteristic angle
RCADir
has the maximum sensitivity. The characteristic for
RCADir
is equal to 0° is shown in Figure
-3V
0
=V
ref
3I
0
RCA = 0
°,
ROA = 90
°
= ang(3I
0
) - ang(3V
ref
)
3I
0
cos
en06000648_ansi.vsd
V
ref
ANSI06000648 V1 EN-US
Figure 81:
Characteristic for RCADir equal to 0°
The characteristic is for
RCADir
equal to -90° is shown in Figure
.
1MRK 511 401-UUS A
Section 8
Current protection
Bay control REC670 2.2 ANSI
197
Application manual