Table 29:
Available selection for voltage quantity within CVGAPC function
Set value for parameter
"VoltageInput"
Comment
1
PhaseA
CVGAPC function will measure the phase A voltage phasor
2
PhaseB
CVGAPC function will measure the phase B voltage phasor
3
PhaseC
CVGAPC function will measure the phase C voltage phasor
4
PosSeq
CVGAPC function will measure internally calculated positive
sequence voltage phasor
5
-NegSeq
CVGAPC function will measure internally calculated negative
sequence voltage phasor. This voltage phasor will be intentionally
rotated for 180° in order to enable easier settings for the directional
feature when used.
6
-3*ZeroSeq
CVGAPC function will measure internally calculated zero sequence
voltage phasor multiplied by factor 3. This voltage phasor will be
intentionally rotated for 180° in order to enable easier settings for
the directional feature when used.
7
MaxPh
CVGAPC function will measure voltage phasor of the phase with
maximum magnitude
8
MinPh
CVGAPC function will measure voltage phasor of the phase with
minimum magnitude
9
UnbalancePh
CVGAPC function will measure magnitude of unbalance voltage,
which is internally calculated as the algebraic magnitude difference
between the voltage phasor of the phase with maximum magnitude
and voltage phasor of the phase with minimum magnitude. Phase
angle will be set to 0° all the time
10
PhaseA-PhaseB
CVGAPC function will measure the voltage phasor internally
calculated as the vector difference between the phase A voltage
phasor and phase B voltage phasor (VA-VB)
11
PhaseB-PhaseC
CVGAPC function will measure the voltage phasor internally
calculated as the vector difference between the phase B voltage
phasor and phase C voltage phasor (VB-VC)
12
PhaseC-PhaseC
CVGAPC function will measure the voltage phasor internally
calculated as the vector difference between the phase C voltage
phasor and phase A voltage phasor (VC-VA)
13
MaxPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the
maximum magnitude
14
MinPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the
minimum magnitude
15
UnbalancePh-Ph
CVGAPC function will measure magnitude of unbalance voltage,
which is internally calculated as the algebraic magnitude difference
between the ph-ph voltage phasor with maximum magnitude and
ph-ph voltage phasor with minimum magnitude. Phase angle will
be set to 0° all the time
It is important to notice that the voltage selection from table
regardless the actual external VT connections. The three-phase VT inputs can be
connected to IED as either three phase-to-groundvoltages VA, VB and VC or three
Section 11
1MRK 511 401-UUS A
Multipurpose protection
272
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...