T1
T2
T3
99000952.VSD
V
1
V
2
V
3
Z
1
Z
2
Z
3
I
1
I
2
I
3
=0
I
L
=I
1
+I
2
ANSI99000952 V1 EN-US
Figure 179:
Disconnection of one transformer in a parallel group
When the busbar arrangement is more complicated with more buses and bus
couplers/bus sections, it is necessary to engineer a specific station topology logic. This
logic can be built in the application configuration in PCM600 and will keep record on
which transformers that are in parallel (in one or more parallel groups). In each
TR8ATCC (90) function block there are eight binary inputs (T1INCLD,..., T8INCLD)
that will be activated from the logic depending on which transformers that are in
parallel with the transformer to whom the TR8ATCC (90) function block belongs.
TR8ATCC (90) function block is also fitted with eight outputs (T1PG,..., T8PG) for
indication of the actual composition of the parallel group that it itself is part of. If
parallel operation mode has been selected in the IED with setting
TrfId
=
Tx
, then the
TxPG signal will always be set to 1. The parallel function will consider communication
messages only from the voltage control functions working in parallel (according to the
current station configuration). When the parallel voltage control function detects that
no other transformers work in parallel it will behave as a single voltage control
function in automatic mode.
Exchange of information between TR8ATCC functions
SEMOD159053-267 v6
Each transformer in a parallel group needs an Automatic voltage control for tap
changer, parallel control TR8ATCC (90) function block of its own for the parallel
voltage control. Communication between these TR8ATCCs (90) is made either on the
GOOSE interbay communication on the IEC 61850 protocol if TR8ATCC (90)
functions reside in different IEDs, or alternatively configured internally in one IED if
multiple instances of TR8ATCC (90) reside in the same IED. Complete exchange of
TR8ATCC (90) data, analog as well as binary, on GOOSE is made cyclically every 300
ms.
TR8ATCC (90) function block has an output ATCCOUT. This output contains two sets
of signals. One is the data set that needs to be transmitted to other TR8ATCC (90)
blocks in the same parallel group, and the other is the data set that is transferred to the
Section 14
1MRK 511 401-UUS A
Control
430
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...