15.1.3.2
Delta blocking scheme
GUID-F4359690-F433-46CB-A173-8C14559E3FCF v1
Set
Operation
=
Enabled
Set
SchemeType
=
DeltaBlocking
Set
tCoord
= 0 s
Set
tSendMin
= 0 s
Set
Unblock
=
Disabled
(Set to
NoRestart if Unblocking scheme with no alarm for loss of guard is to be
used.
Set to
Restart if Unblocking scheme with alarm for loss of guard is to be used)
Set
tSecurity
= 0.035 s
Set
DeltaI
= 10 %IB
Set
DeltaV
= 5 %VB
Set
Delta3I0
= 10 %IB
Set
Delta3V0
= 5 %VB
15.1.3.3
Permissive underreaching scheme
M13869-25 v4
Set
Operation
=
Enabled
Set
SchemeType
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
Set
Unblock
=
Disabled
Set
tSecurity
= 0.035 s
15.1.3.4
Permissive overreaching scheme
M13869-34 v4
Set
Operation
=
Enabled
Set
Scheme type
=
Permissive OR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Disabled
Set
tSecurity
= 0.035 s
15.1.3.5
Unblocking scheme
M13869-43 v4
Set
Unblock
=
Restart
(Loss of guard signal will give both trip and alarm
Choose
NoRestart if only trip is required)
Set
tSecurity
= 0.035 s
1MRK 511 401-UUS A
Section 15
Scheme communication
Bay control REC670 2.2 ANSI
473
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...