23.6
Summation block 3 phase 3PHSUM
SEMOD55968-1 v2
23.6.1
Application
SEMOD56004-4 v3
The analog summation block 3PHSUM function block is used in order to get the sum
of two sets of 3 phase analog signals (of the same type) for those IED functions that
might need it.
23.6.2
Setting guidelines
SEMOD56006-4 v6
The summation block receives the three-phase signals from SMAI blocks. The
summation block has several settings.
SummationType
: Summation type (
Group 1 + Group 2
,
Group 1 - Group 2
,
Group 2 -
Group 1
or
–(Group 1 + Group 2)
).
DFTReference
: The reference DFT block (
InternalDFT Ref
,
DFTRefGrp1
or
External
DFT ref
) .
FreqMeasMinVal
: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of
VBase
base voltage setting (for each instance x).
GlobalBaseSel
: Selects the global base value group used by the function to define
(
IBase
), (
VBase
) and (
SBase
).
23.7
Global base values GBASVAL
GUID-2FDB0A2C-10FE-4954-B6E4-9DA2EEEF1668 v1
23.7.1
Identification
GUID-0D5405BE-E669-44C8-A208-3A4C86D39115 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Global base values
GBASVAL
-
-
1MRK 511 401-UUS A
Section 23
Basic IED functions
Bay control REC670 2.2 ANSI
611
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...