Test point
Reach
Set value
Comments
12
X
0.5 x X1
set
R
0.5 x R1
set
13
X
0
Only used when
OperationLdCmp setting is 0
(Off)
R
0.5 x RFPP
Table 24: Test points for phase-to-earth L3-E (Ohm/Loop)
Test point
Reach
Value
Comments
1
X
(2 x X1
set
+X0
set
)/3
R
0
2
X
(2 x X1
set
+ X0
set
)/3
R
2 x R1
set
+ R0
set
)/3
3
X
0.8 x (2 x X1
set
+ X0
set
)/3
R
0.8 x (2 x R1
set
+ R0
set
)/3
+RFPE
set
4
X
0.5 x (2 x X1
set
+ R0
set
)/3
R
0.5 x (2 x R1
set
+R0
set
)/3 +
RFPE
set
5
X
0.85 x RFPE
set
x tan(ArgLdset)
ArgLd = angle for the maximal load transfer.
R
0.85 x RFPE
6
X
RLdFwset x tan(ArgLdSet)
R
RLdFw
set
7
X
0
R
RLdFw
set
8
X
–02143 x RLdFw
set
Exact: 0.8 x RFPE x tan (ArgDir)
R
0.8 x RLdFw
set
9
X
–0.8 x RLdFw
set
x tan(ArgDir)
R
0.8 x RLdFw
set
10
X
0.17 x (2 x X1
set
+ X0
set
)
Exact: 0.5 x (2 x X1
set
X0
set
)/3
R
-0.36 x (2 x X1
set
+ X0
set
)
Exact: 0.5 x (2X1
set
+ X0
set
)/(3 x tan(AgNegDir90)
11
X
0.27 x (2 x X1
set
+X0
set
)
Exact: 0.8 x (2 x X1
set
+ X0
set
)/3
R
–0.57 x (2 x X1
set
+ X0
set
)
Exact: 0.8 x ( X0set)/(3 x tan(AngNegDir
90))
12
X
0.5 x (2 x X1
set
+ X0
set
)/3
R
0.5 x (2 x R1
set
+ R0
set
)/3
13
X
0
R
RFPE
12.4.5.1
Measuring the operating limit of set values
GUID-02EE80DB-CE52-49F0-99C4-14FD84766009 v3
Procedure:
Section 12
1MRK 502 067-UEN B
Testing functionality by secondary injection
114
Commissioning manual