The internal events in this list not only refer to faults in the IED, but also to other activities,
such as change of settings, clearing of disturbance reports, and loss of external time
synchronization.
The information can only be retrieved from the Parameter Setting software package. The PC
can be connected either to the port at the front or at the rear of the IED.
These events are logged as internal events.
Table 36: Events available for the internal event list in the IED
Event message:
Description
Generating signal:
INT--FAIL
Off
Internal fail status
INT--FAIL (reset event)
INT--FAIL
INT--FAIL (set event)
INT--WARNING
Off
Internal warning status
lNT--WARNING (reset event)
INT--WARNING
lNT--WARNING (set event)
IOn--Error
Off
In/Out module No. n status
IOn--Error (reset event)
IOn--Error
IOn--Error (set event)
ADMn-Error
Off
Analog/Digital module No. n
status
ADMn-Error (reset event)
ADMn-Error
ADMn-Error (set event)
MIM1-Error
Off
mA-input module status
MIM1-Error (reset event)
MIM1-Error
MIM1-Error (set event)
INT--RTC
Off
Real Time Clock (RTC) status
INT--RTC (reset event)
INT--RTC
INT--RTC (set event)
INT--TSYNC
Off
External time synchronization
status
INT--TSYNC (reset event)
INT--TSYNC
INT--TSYNC (set event)
INT--SETCHGD
Any settings in IED changed
DRPC-CLEARED
All disturbances in
Disturbance report cleared
The events in the internal event list are time tagged with a resolution of 1ms.
This means that, when using the PC for fault tracing, it provides information on the:
•
Module that should be changed.
•
Sequence of faults, if more than one unit is faulty.
•
Exact time when the fault occurred.
15.2.3
Diagnosing the IED status via the LHMI hint menu
GUID-7E8503E9-441B-487A-9CD7-B43463D1CAE5 v3
In order to help the user, there is an LHMI page labeled ‘Hints’. This page is located under Main
menu/Diagnostics/IED status/Hints. For each activated hint there is a headline. From the
headline view, an explanation page can be entered, giving the user more information and hints
about the particular topic.
For example, if there is a configuration to use IEC 61850 9–2 analog data, but no data arrives
on the access point, then the IED will use substituted data and most protection functions will
be blocked. This condition will be indicated with a sub-menu under Hints, where details about
this condition are shown. The Hint menu is a way to assist the user in troubleshooting.