xx04000310-1-en.vsd
t (s)
0
t1
t2
1
3
2
IEC04000310 V2 EN-US
Figure 2:
Typical IED start-up sequence
1 IED energized. Green LED instantly starts flashing
2 LCD lights up and "IED startup" is displayed
3 The main menu is displayed. A steady green light indicates a successful startup.
If the upper row in the window indicates ‘Fail’ instead of ‘Ready’ and the green LED flashes, an
internal failure in the IED has been detected. See section
"Checking the self supervision
4.5
Energizing REX060
4.5.1
REX060 start up sequence
GUID-63A15CD3-17B0-41DD-9611-8272DDA53137 v1
When the injection unit REX060 is energized, the ABB logotype is shown followed by current
REX060 revision status. When the start up sequence is completed, the main menu (normal
display content) is shown. The duration of the start up sequence is a few seconds.
4.6
Setting up communication between PCM600 and the
IED
SEMOD58570-5 v12
The communication between the IED and PCM600 is independent of the communication
protocol used within the substation or to the NCC.
The communication media is always Ethernet and the used protocol is TCP/IP.
Each IED has an RJ-45 Ethernet interface connector on the front. The front Ethernet connector
shall be used for communication with PCM600.
When an Ethernet-based station protocol is used, PCM600 communication can use the same
Ethernet port and IP address.
To connect PCM600 to the IED, two basic variants must be considered.
•
Direct point-to-point link between PCM600 and the IED front port. The front port can be
seen as a service port.
•
Indirect link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enable
communication.
The communication procedures are the same in both cases.
1MRK 502 067-UEN B
Section 4
Starting up
41
Commissioning manual