18.3.6.3
Signals
Table 732:
PRPSTATUS Output signals
Name
Type
Description
PRP-A LINK
BOOLEAN
PRP-A Link Status
PRP-A VALID
BOOLEAN
PRP-A Link Valid
PRP-B LINK
BOOLEAN
PRP-B Link Status
PRP-B VALID
BOOLEAN
PRP-B Link Valid
18.3.6.4
Settings
Table 733:
PRP Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
PRPMode
PRP-0
PRP-1
-
-
PRP-1
PRP Mode
IPAddress
0 - 18
IP
Address
1
192.168.7.10
IP-Address
IPMask
0 - 18
IP
Address
1
255.255.255.0
IP-Mask
18.3.6.5
Monitored data
Table 734:
PRPSTATUS Monitored data
Name
Type
Values (Range)
Unit
Description
AB Beh
INTEGER
2=Blocked
3=Test
4=Test blocked
5=Off
1=On
-
AB Link Beh
CD Beh
INTEGER
1=On
2=Blocked
3=Test
4=Test blocked
5=Off
-
CD Link Beh
PRP Beh
INTEGER
2=Blocked
3=Test
4=Test blocked
5=Off
1=On
-
PRP Beh
18.3.6.6
Principle of operation
The communication is performed in parallel, that is the same data package is
transmitted on both channels simultaneously. The received package identity from one
channel is compared with data package identity from the other channel, if they are the
Section 18
1MRK502052-UEN B
Station communication
1000
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...