Name
Values (Range)
Unit
Step
Default
Description
MaxUL1
0.05 - 2000.00
kV
0.05
230.00
Maximum voltage for phase L1
MaxUL2
0.05 - 2000.00
kV
0.05
230.00
Maximum voltage for phase L2
MaxUL3
0.05 - 2000.00
kV
0.05
230.00
Maximum voltage for phase L3
MaxUL1-UL2
0.05 - 2000.00
kV
0.05
400.00
Maximum voltage for phase-phase L1-L2
MaxUN
0.05 - 2000.00
kV
0.05
230.00
Maximum residual voltage UN
MaxP
0.00 - 2000.00
MW
0.05
1200.00
Maximum value for active power
MaxQ
0.00 - 2000.00
MVAr
0.05
1200.00
Maximum value for reactive power
MaxF
45.0 - 66.0
Hz
1.0
51.0
Maximum system frequency
18.6.3
Measurands user defined signals for IEC 60870-5-103
I103MEASUSR
18.6.3.1
Functionality
I103MEASUSR is a function block with user defined input measurands in monitor
direction. These function blocks include the
FunctionType
parameter for each block
in the private range, and the Information number parameter for each block.
18.6.3.2
Identification
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measurands user defined signals for
IEC 60870-5-103
I103MEASUSR
-
-
18.6.3.3
Function block
IEC10000288-1-en.vsd
I103MEASUSR
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
IEC10000288 V1 EN
Figure 472:
I103MEASUSR function block
Section 18
1MRK502052-UEN B
Station communication
1032
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...