setting the
Report Intermediate Position
=
Off
. See the settings for RS485 and optical
serial communication for more information.
Input SELECT is a single-indication signal, and it is also GI enabled. State transitions
to ON and OFF are reported spontaneously.
When input BLOCK is ON, the function will ignore GI requests and cease all
monitoring activity. Consequently, no transitions will be detected.
The I103POSCMD function is also equipped with two additional commands: Operate
and Cancel. These are hidden in ACT and respond only to base INF +2 and +3
respectively. The base INF (Information Number) parameter is an IEC 60870-5-103
identifier that associates a function in a 103 Master (such as Scada) with its equivalent
in the IED.
18.6.14.2
Identification
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED commands with position and select
for IEC 60870-5-103
I103POSCMD
-
-
18.6.14.3
Function block
IEC10000286-1-en.vsd
I103POSCMD
BLOCK
POSITION
SELECT
IEC10000286 V1 EN
Figure 483:
I103POSCMD function block
18.6.14.4
Signals
Table 775:
I103POSCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
POSITION
INTEGER
0
Position of controllable object
SELECT
BOOLEAN
0
Select of controllable object
18.6.14.5
Settings
Table 776:
I103POSCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type
InfNo
160 - 236
-
4
160
Information number for command output
1MRK502052-UEN B
Section 18
Station communication
1049
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...