The input of this GOOSE block must be linked in SMT by means of
a cross to receive the binary single point values.
The implementation for IEC 61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the
DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
18.13
MULTICMDRCV and MULTICMDSND
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multiple command and receive
MULTICMDRCV
-
-
Multiple command and send
MULTICMDSND
-
-
18.13.1
Functionality
The IED provides two function blocks enabling several IEDs to send and receive
signals via the interbay bus. The sending function block, MULTICMDSND, takes 16
binary inputs. LON enables these to be transmitted to the equivalent receiving
function block, MULTICMDRCV, which has 16 binary outputs.
18.13.2
Design
18.13.2.1
General
The common behavior for all 16 outputs of the MULTICMDRCV is set to either of
two modes: Steady or Pulse.
•
1 = Steady: This mode simply forwards the received signals to the binary outputs.
•
2 = Pulse: When a received signal transitions from 0 (zero) to 1 (one), a pulse with
a duration of exactly one execution cycle is triggered on the corresponding binary
output. This means that no connected function block may have a cycle time that
is higher than the execution cycle time of the particular MULTICMDRCV
instance.
1MRK502052-UEN B
Section 18
Station communication
1073
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...