20.18.4
Settings
Settings
DFTRefExtOut
and
DFTReference
shall be set to default
value
InternalDFTRef
if no VT inputs are available.
Table 871:
3PHSUM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
SummationType
Group2
Group1-Group2
Group2-Group1
-(Group2)
-
-
Group2
Summation type
DFTReference
InternalDFTRef
DFTRefGrp1
External DFT ref
-
-
InternalDFTRef
DFT reference
DFTRefExtOut
InternalDFTRef
DFTRefGrp1
External DFT ref
-
-
InternalDFTRef
DFT reference for external output
Table 872:
3PHSUM Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
FreqMeasMinVal
5 - 200
%
1
10
Amplitude limit for frequency calculation in
% of UBase
20.18.5
Operation principle
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal
matrix for analog inputs function (SMAI). In the same way, the BLOCK input will
reset all the outputs of the function to 0.
20.19
Denial of service DOS
20.19.1
Functionality
The Denial of service functions (DOSFRNT, DOSLANAB and DOSLANCD) are
designed to limit overload on the IED produced by heavy Ethernet network traffic.
The communication facilities must not be allowed to compromise the primary
functionality of the device. All inbound network traffic will be quota controlled so that
too heavy network loads can be controlled. Heavy network load might for instance be
the result of malfunctioning equipment connected to the network.
1MRK502052-UEN B
Section 20
Basic IED functions
1137
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...