Name
Type
Values (Range)
Unit
Description
BO23
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 23 status
BO24VALUE
BOOLEAN
1=1
0=0
-
Binary output 24 value
BO24FORCE
BOOLEAN
0=Normal
1=Forced
-
nary output 24 force
BO24
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 24 status
21.2.8.6
Technical data
Table 899:
BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Trip and Signal relays
Binary outputs
24
Max system voltage
250 V AC, DC
Test voltage across open contact, 1 min
1000 V rms
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous
8 A
10 A
12 A
Making capacity at inductive load with L/R>10 ms
0.2 s
1.0 s
30 A
10 A
Breaking capacity for AC, cos
j
>0.4
250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Maximum 72 outputs may be activated simultaneously. After 6 ms an
additional 24 outputs may be activated. The activation time for the 96
outputs must not exceed 200 ms. 48 outputs can be activated during 1
s. Continued activation is possible with respect to current
consumption but after 5 minutes the temperature rise will adversely
affect the hardware life. Maximum two relays per BOM/IOM should
be activated continuously due to power dissipation.
Section 21
1MRK502052-UEN B
IED hardware
1168
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...