21.2.9.6
Technical data
Table 904:
SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity
Static binary output trip
Rated voltage
48-60 VDC
110-250 VDC
Number of outputs
6
6
Impedance open state
~300 kΩ
~810 kΩ
Test voltage across open contact, 1
min
No galvanic separation
No galvanic separation
Current carrying capacity:
Continuous
5 A
5 A
1.0 s
10 A
10 A
Making capacity at capacitive load
with the maximum capacitance of
0.2 μF :
0.2 s
30 A
30 A
1.0 s
10 A
10 A
Breaking capacity for DC with L/R ≤
40 ms
48 V/1 A
110 V/0.4 A
60 V/0.75 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Operating time
< 1 ms
< 1 ms
Table 905:
SOM - Static Output module data (reference standard: IEC 61810-2):
Electromechanical relay outputs
Function of quantity
Trip and signal relays
Max system voltage
250 V AC/DC
Number of outputs
6
Test voltage across open contact, 1 min
1000 V rms
Current carrying capacity:
Continuous
8 A
1.0 s
10 A
Making capacity at capacitive load with the
maximum capacitance of 0.2 μF:
0.2 s
30 A
1.0 s
10 A
Breaking capacity for DC with L/R ≤ 40 ms
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
1MRK502052-UEN B
Section 21
IED hardware
1173
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...