Maximum 72 outputs may be activated simultaneously with
influencing factors within nominal range. After 6 ms an additional 24
outputs may be activated. The activation time for the 96 outputs must
not exceed 200 ms. 48 outputs can be activated during 1 s. Continued
activation is possible with respect to current consumption but after 5
minutes the temperature rise will adversely affect the hardware life.
Maximum two relays per BOM/IOM/SOM should be activated
continuously due to power dissipation.
21.2.10
Binary input/output module (IOM)
21.2.10.1
Introduction
The binary input/output module is used when only a few input and output channels are
needed. The ten standard output channels are used for trip output or any signaling
purpose. The two high speed signal output channels are used for applications where
short operating time is essential. Eight optically isolated binary inputs cater for
required binary input information.
21.2.10.2
Design
The binary input/output module is available in two basic versions, one with
unprotected contacts and one with MOV (Metal Oxide Varistor) protected contacts.
Inputs are designed to allow oxide burn-off from connected contacts, and increase the
disturbance immunity during normal protection operate times. This is achieved with
a high peak inrush current while having a low steady-state current, see figure
.
Inputs are debounced by software.
Well defined input high and input low voltages ensures normal operation at battery
supply earth faults, see figure
The voltage level of the inputs is selected when ordering.
I/O events are time stamped locally on each module for minimum time deviance and
stored by the event recorder if present.
The binary I/O module, IOM, has eight optically isolated inputs and ten output relays.
One of the outputs has a change-over contact. The nine remaining output contacts are
connected in two groups. One group has five contacts with a common and the other
group has four contacts with a common, to be used as single-output channels, see
figure
.
The binary I/O module also has two high speed output channels where a reed relay is
connected in parallel to the standard output relay.
For configuration of the input and output signals, refer to sections
"Signal matrix for binary outputs SMBO"
.
Section 21
1MRK502052-UEN B
IED hardware
1174
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...