xx04000155.vsd
1
2
4
3
5
6
7
IEC04000155 V2 EN
Figure 545:
Antenna with console
where:
1
GPS antenna
2
TNC connector
3
Console, 78x150 mm
4
Mounting holes 5.5 mm
5
Tab for securing of antenna cable
6
Vertical mounting position
7
Horizontal mounting position
Antenna cable
Use a 50 ohm coaxial cable with a male TNC connector in the antenna end and a male
SMA connector in the receiver end to connect the antenna to GTM. Choose cable type
and length so that the total attenuation is max. 26 dB at 1.6 GHz.
Make sure that the antenna cable is not charged when connected to the
antenna or to the receiver. Short-circuit the end of the antenna cable
with some metal device, when first connected to the antenna. When
the antenna is connected to the cable, connect the cable to the receiver.
The IED must be switched off when the antenna cable is connected.
1MRK502052-UEN B
Section 21
IED hardware
1197
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...