Test
Type test values
Reference standards
Pulse magnetic field
immunity test
1000 A/m
IEC 61000–4–9, Class V
Damped oscillatory magnetic
field test
100 A/m
IEC 61000-4-10, Class V
Radiated electromagnetic
field disturbance
20 V/m, 80-1000 MHz
1.4-2.7 GHz
IEC 60255-26
Radiated electromagnetic
field disturbance
20 V/m
80-1000 MHz
IEEE/ANSI C37.90.2
Conducted electromagnetic
field disturbance
10 V, 0.15-80 MHz
IEC 60255-26
Radiated emission
30-5000 MHz
IEC 60255-26
Radiated emission
30-5000 MHz
IEEE/ANSI C63.4, FCC
Conducted emission
0.15-30 MHz
IEC 60255-26
Table 941:
Insulation
Test
Type test values
Reference standard
Dielectric test
2.0 kV AC, 1 min.
IEC 60255-27
ANSI C37.90
Impulse voltage test
5 kV, 1.2/50
m
s, 0.5 J
Insulation resistance
>100 M
W
at 500 VDC
Table 942:
Environmental tests
Test
Type test value
Reference standard
Cold operation test
Test Ad for 16 h at -25°C
IEC 60068-2-1
Cold storage test
Test Ab for 16 h at -40°C
IEC 60068-2-1
Dry heat operation test
Test Bd for 16 h at +70°C
IEC 60068-2-2
Dry heat storage test
Test Bb for 16 h at +85°C
IEC 60068-2-2
Change of temperature test
Test Nb for 5 cycles at -25°C
to +70°C
IEC 60068-2-14
Damp heat test, steady state
Test Ca for 10 days at +40°C
and humidity 93%
IEC 60068-2-78
Damp heat test, cyclic
Test Db for 6 cycles at +25 to
+55°C and humidity 93 to
95% (1 cycle = 24 hours)
IEC 60068-2-30
Table 943:
CE compliance
Test
According to
Immunity
EN 60255–26
Emissivity
EN 60255–26
Low voltage directive
EN 60255–27
Section 21
1MRK502052-UEN B
IED hardware
1218
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...