Table 948:
REX060 Power supply Technical data
Quantity
Rated value
Nominal range
Auxiliary dc voltage, EL (input)
EL = (24 – 60) V
EL = (90 – 250) V
EL ±20%
EL ±20%
Power consumption
30 W
–
Auxiliary DC power in-rush
< 5 A during 0.1 s
–
Table 949:
REX061 Technical data
Function
Range or values
Accuracy
For machines with:
•
rated field voltage up to 800 V DC
-
•
static exciter with rated
supply voltage up to
1600 V 50/60 Hz
-
Specifications
Values
Case size
218 x 150 x 243 mm (W x D x H)
Weight
4.8 kg
Assembling
6 x 5 mm screws (3 at bottom and 3 at top)
Rated rotor injection voltage
250 V
Burden, static excitation system X1:1 to X1:7
<
0.5 VA at 100 V external disturbance
Burden, static excitation system X1:1 or X1:7 to
0 V
<
1.0 VA at 100 V external disturbance
Burden, brushless excitation system X1:1 and
X1:7 to 0 V
<
1.5 VA at 100 V external disturbance
Installation category
III
Pollution degree
2
Table 950:
REX062 Technical data
Specifications
Values
Case size
218 x 150 x 243 mm (W x D x H)
Weight
4.5 kg
Assembling
6 x 5 mm screws (3 at bottom and 3 at top)
Rated stator injection voltage
240 V
Rated stator voltage
240 V
Burden, injection X1:2 and X1:4
<
25 VA at 12 V earth fault voltage
<
100 VA at 24 V earth fault voltage
Installation category
III
Pollution degree
2
1MRK502052-UEN B
Section 22
Injection equipment hardware
1233
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...