Table 953:
Insulation tests, REX060, REX062 and REG670
Test
Type test values
Reference standard
Dielectric test
2.0 kV AC, 1 min
IEC 60255-27
Impulse voltage test
5.0 kV, 1.2/50 µs, 0.5 J
IEC 60255-27
Insulation resistance
>100 MΩ at 500V DC
IEC 60255-27
Table 954:
Insulation tests, REX061
Test
Type test values
Reference standard
Dielectric test
7.48 kV DC, 1min
(connections to rotor)
2.8 kV DC, 1 min
IEEE 421.3
IEC 60255-27
Impulse voltage test
12.0 kV, 1.2/50 µs, 0.5 J
(connections to rotor)
5.0 kV, 1.2/50 µs, 0.5 J
IEC 60664-1
IEC 60255-27
Insulation resistance
>100 MΩ at 500V DC
IEC 60255-27
Table 955:
Mechanical tests
Test
Reference standards
Requirements
Vibration response test
IEC 60255-21-1
Class 2
Vibration endurance test
REG670 and REX060
REX061 and REX062
IEC 60255-21-1
Class 1
Class 2
Shock response test
REG670 and REX060
REX061 and REX062
IEC 60255-21-2
Class 1
Class 2
Shock withstand test
REG670 and REX060
REX061 and REX062
IEC 60255-21-2
Class 1
Class 2
Bump test
REG670 and REX060
REX061 and REX062
IEC 60255-21-2
Class 1
Class 2
Seismic test
REG670 and REX060
REX061 and REX062
IEC 60255-21-3
Class 2
Class 2 extended
1MRK502052-UEN B
Section 22
Injection equipment hardware
1235
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...