Table 88:
ZMFPDIS Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
ZoneLinkStart
Phase Selection
1st starting zone
-
-
Phase Selection
Select. of start source for all ZoneLinked
trip delay timers
INReleasePE
5 - 400
%IPh
1
400
3I0 limit for releasing Phase-to-Earth
measuring loops
TimerModeZ1
Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone 1
TimerLinksZ1
LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
-
LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 1
TimerModeZ2
Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone 2
TimerLinksZ2
LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
-
LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 2
TimerModeZ3
Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone 3
TimerLinksZ3
LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
-
LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 3
TimerModeZ4
Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone 4
TimerLinksZ4
LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
-
LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 4
TimerModeZ5
Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone 5
TimerLinksZ5
LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
-
LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone 5
TimerModeZRV
Disable all
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
output, zone RV
TimerLinksZRV
LoopLink (tPP-tPE)
LoopLink &
ZoneLink
No Links
-
-
LoopLink (tPP-
tPE)
How start of trip delay timers should be
linked for zone RV
1MRK502052-UEN B
Section 7
Impedance protection
211
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...