Table 89:
ZMFPDIS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
7.3.6
Monitored data
Table 90:
ZMFPDIS Monitored data
Name
Type
Values (Range)
Unit
Description
L1Dir
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction in phase L1
L2Dir
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction in phase L2
L3Dir
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction in phase L3
L1L2Dir
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction in loop L1L2
L2L3Dir
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction in loop L2L3
L3L1Dir
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction in loop L3L1
L1R
REAL
-
Ohm
Resistance in phase L1
L1X
REAL
-
Ohm
Reactance in phase L1
L2R
REAL
-
Ohm
Resistance in phase L2
L2X
REAL
-
Ohm
Reactance in phase L2
L3R
REAL
-
Ohm
Resistance in phase L3
L3X
REAL
-
Ohm
Reactance in phase L3
7.3.7
Operation principle
Settings, input and output names are sometimes mentioned in the following text
without its zone suffix (i.e. BLKZx instead of BLKZ3) when the description is equally
valid for all zones.
7.3.7.1
Filtering
Practically all voltage, current and impedance quantities used within the ZMFPDIS
function are derived from fundamental frequency phasors filtered by a half cycle
filter.
Section 7
1MRK502052-UEN B
Impedance protection
212
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...