Name
Values (Range)
Unit
Step
Default
Description
R0FwPEZ1
0.00 - 3000.00
Ohm/p
0.01
15.00
Zero seq. resistive reach, Ph-E, zone 1,
forward direction
RFPEZ1
0.01 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach, Ph-E, zone 1, forw
& rev dir.
X1RvPEZ1
0.01 - 3000.00
Ohm/p
0.01
30.00
Pos. seq. react. reach, Ph-E, zone 1,
reverse direction
tPPZ1
0.000 - 60.000
s
0.001
0.000
Time delay to trip, Phase-Phase, zone 1
tPEZ1
0.000 - 60.000
s
0.001
0.000
Time delay to trip, Phase-Earth, zone 1
IMinOpPPZ1
5 - 6000
%IB
1
10
Minimum operate ph-ph current for
Phase-Phase loops, zone 1
IMinOpPEZ1
5 - 6000
%IB
1
10
Minimum operate phase current for
Phase-Earth loops, zone 1
OpModeZ2
Disable-Zone
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E loops,
zone 2
X1FwPPZ2
0.01 - 3000.00
Ohm/p
0.01
40.00
Positive seq. reactance reach, Ph-Ph,
zone 2, forward dir.
R1FwPPZ2
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistive reach, Ph-Ph, zone
2, forward dir.
RFPPZ2
0.01 - 9000.00
Ohm/l
0.01
30.00
Fault resistance reach, Ph-Ph, zone 2,
forw & rev dir.
X1RvPPZ2
0.01 - 3000.00
Ohm/p
0.01
40.00
Pos. seq. react. reach, Ph-Ph, zone 2,
reverse direction
X1FwPEZ2
0.01 - 3000.00
Ohm/p
0.01
40.00
Positive seq. reactance reach, Ph-E, zone
2, forward dir.
R1FwPEZ2
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistive reach, Ph-E, zone
2, forward dir.
X0FwPEZ2
0.01 - 9000.00
Ohm/p
0.01
120.00
Zero seq. reactance reach, Ph-E, zone 2,
forward direction
R0FwPEZ2
0.00 - 3000.00
Ohm/p
0.01
15.00
Zero seq. resistive reach, Ph-E, zone 2,
forward direction
RFPEZ2
0.01 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach, Ph-E, zone 2, forw
& rev dir.
X1RvPEZ2
0.01 - 3000.00
Ohm/p
0.01
40.00
Pos. seq. react. reach, Ph-E, zone 2,
reverse direction
tPPZ2
0.000 - 60.000
s
0.001
0.400
Time delay to trip, Phase-Phase, zone 2
tPEZ2
0.000 - 60.000
s
0.001
0.400
Time delay to trip, Phase-Earth, zone 2
IMinOpPPZ2
5 - 6000
%IB
1
10
Minimum operate ph-ph current for
Phase-Phase loops, zone 2
IMinOpPEZ2
5 - 6000
%IB
1
10
Minimum operate phase current for
Phase-Earth loops, zone 2
OpModeZ3
Disable-Zone
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E loops,
zone 3
DirModeZ3
Non-directional
Forward
Reverse
-
-
Forward
Direction of zone 3 (which will be the Fw
direction of zone 3)
Table continues on next page
Section 7
1MRK502052-UEN B
Impedance protection
232
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...