Name
Type
Description
SFREQ
REAL
Slip frequency
SLIPZOHM
REAL
Slip impedance in ohms
SLIPZPER
REAL
Slip impedance in percent of ZBase
UCOS
REAL
UCosPhi voltage
UCOSPER
REAL
UCosPhi voltage in percent of UBase
7.5.5
Settings
Table 101:
PSPPPAM Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation On / Off
OperationZ1
Off
On
-
-
On
Operation Zone1 On / Off
OperationZ2
Off
On
-
-
On
Operation Zone2 On / Off
ImpedanceZA
0.00 - 1000.00
%
0.01
10.00
Forward impedance in % of Zbase
ImpedanceZB
0.00 - 1000.00
%
0.01
10.00
Reverse impedance in % of Zbase
ImpedanceZC
0.00 - 1000.00
%
0.01
10.00
Impedance of zone1 limit in % of Zbase
AnglePhi
72.00 - 90.00
Deg
0.01
85.00
Angle of the slip impedance line
StartAngle
0.0 - 180.0
Deg
0.1
110.0
Rotor angle for the start signal
TripAngle
0.0 - 180.0
Deg
0.1
90.0
Rotor angle for the trip1 and trip2 signals
N1Limit
1 - 20
-
1
1
Count limit for the trip1 signal
N2Limit
1 - 20
-
1
3
Count limit for the trip2 signal
Table 102:
PSPPPAM Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
ResetTime
0.000 - 60.000
s
0.001
5.000
Time without slip to reset all signals
Table 103:
PSPPPAM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
MeasureMode
PosSeq
L1L2
L2L3
L3L1
-
-
PosSeq
Measuring mode (PosSeq, L1L2, L2L3,
L3L1)
InvertCTcurr
No
Yes
-
-
No
Invert current direction
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
Section 7
1MRK502052-UEN B
Impedance protection
254
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...