The TRIP1 tripping command and signal are generated after N1 slips in zone 1,
providing the rotor angle is less than
TripAngle
. The TRIP2 signal is generated after
N2 slips in zone 2, providing the rotor angle is less than
TripAngle
.
All signals are reset if:
•
the direction of movement reverses
•
the rotor angle detector resets without a slip being counted or
•
no rotor relative movement was detected during the time
ResetTime
.
Ucos
< 0.92 UBase
IEC07000005.vsd
Imin > 0.10 IBase
0.2
Slip.Freq.
8 Hz
AND
startAngle
AND
START
Z cross line ZA - ZC
Z cross line ZC - ZB
AND
AND
ZONE1
ZONE2
Counter
N1Limit
a
b
a
b
tripAngle
AND
TRIP1
Counter
N2Limit
a
b
a
b
AND
TRIP2
OR
TRIP
IEC07000005 V2 EN
Figure 109:
Simplified logic diagram for pole slip protection PSPPPAM
Section 7
1MRK502052-UEN B
Impedance protection
258
Technical manual