degrees. It can be observed in Figure
that the angle reaches 180 degrees when the
complex impedance Z(R, X) crosses the impedance line SE – RE. It then changes the
sign, and continues from -180 degrees to 0 degrees, and so on. Figure
rotor (power) angle and the magnitude of Z(R, X) against time for the case from Figure
0
200
400
600
800
1000
1200
1400
-4
-3
-2
-1
0
1
2
3
4
Time in millis econds
®
Im
pe
da
nc
e
Z
in
O
hm
a
nd
r
ot
or
a
ng
le
in
r
ad
ia
n
®
|Z| in Ohms
angle in rad
normal
load
fault 500 ms
Z(R,X) cros s e d
the im pe da nce line , Z-line ,
conne cting points S E - RE
fault
occurrs
Z(R, X) under fault lies
on the impedance line
or near (for 3-ph faults )
Unde r 3-pha s e fa ult
condition rotor a ngle
of a pp. ±180 de gre e s
is m e a s ure d ...
rotor (power)
angle
|Z|
IEC10000110-2-en.vsd
1
2
3
1
0
IEC10000110 V2 EN
Figure 112:
Rotor (power) angle and magnitude of the complex impedance Z(R,
X) against the time
In order to be able to fully understand the principles of OOSPPAM, a stable case, that
is, a case where the disturbance does not make a generator to go out-of-step, must be
shown.
Section 7
1MRK502052-UEN B
Impedance protection
264
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...