7.8.9.4
Simplified logic diagram
Uinj
Rshunt
ROTIPHIZ
REX060
REG670
1
I
U
u_i_ref
u_u_ref
X
S
K1
K2
Compare &
Evaluate
ZRef1
ZRef2
3
2
4
5
6
7
IEC10000327-2-en.vsd
Bare
Z
Measured
Z
Inj
I
Inj
U
¸
R
f
IEC10000327 V1 EN
Figure 129:
Simplified logic diagram for sensitive rotor earth fault protection,
injection based ROTIPHIZ
1
The sensitive rotor earth fault protection function receives amplified injected voltage and
current via the REX060 unit as two voltages signals. (Voltage inputs in the IED)
2
The phasor of injected voltage U
Inj
and phasor of injected current I
Inj
is calculated by using
special filter from raw samples. Observe that phasors are calculated for the injected
frequency.
3
The complex bare impedance is calculated from U
inj
/ I
inj
.
4, 5
The complex measured impedance is derived as Z
Measured
= Z
bare
*
k1 + k2 [Ω].
6
The fault resistance (R
f
) is calculated from the complex measured impedance and a selected
complex reference.
7
Selection of one (out of maximum 2) Z
Ref
.
Section 7
1MRK502052-UEN B
Impedance protection
290
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...