Trip time
Fault resistance
R
Trip
R
Alarm
IEC11000002-1-en.vsd
10
FilterLength
×
2
FilterLength
×
IEC11000002 V1 EN
Figure 131:
Trip time characteristic as function of fault resistance
A third high level step for the detection of excitation system earth faults on the AC side
of the excitation rectifier is available. This step uses the network frequency (50 or 60
Hz) for the evaluation. If an earth fault occurs at the AC side of the excitation system
rectifier, there is a fundamental frequency component at the measured voltage and
current injection points.
The third high level step is not applicable if mixed signals are used, that is when the
REX060 is used for both rotor and stator earth fault protection and only two, instead
of four, analog inputs on the IED are used.
7.8.10
Technical data
Table 132:
ROTIPHIZ technical data
Function
Range or value
Accuracy
Fault resistance sensitivity
Can be reached at
steady state operating
condition of the
machine
500 kΩ
Typically
20 - 50 kΩ
Injection frequency
(75.000 - 250.000) Hz
±0.1 Hz
Trip limit of fault resistance
(100 - 100000)Ω
5% of 1 kΩ at R
f
≤ 1 kΩ
5% of set value at 1 kΩ < R
f
≤ 20 kΩ
10% of set value at R
f
> 20 kΩ
Table continues on next page
Section 7
1MRK502052-UEN B
Impedance protection
292
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...