The injection equipment provides calculation of the fault resistance:
•
If the fault resistance is equal or below 10 kΩ, RFAULT is displayed in Ω
•
If the fault resistance is above 10 kΩ, RFAULT is initially displayed as -1000
until the fault resistance has reached a stable value and then displayed in Ω
•
RFAULT displayed as -2000 means error
7.9.5
Function block
STTIPHIZ
USU*
USI*
BLOCK
ZREFSEL
TRIP
START
ALARM
OPCIRC
ERROR
ERRSTAT
RAVE
XAVE
FREQU
RFAULT
ZREF
ZREFRE
ZREFIM
URMSSTAT
IEC10000298-2-en.vsd
IEC10000298 V1 EN
Figure 132:
STTIPHIZ function block
7.9.6
Signals
Table 136:
STTIPHIZ Input signals
Name
Type
Default
Description
USU
GROUP
SIGNAL
-
Injected voltage signal
USI
GROUP
SIGNAL
-
Injected current signal (voltage over shunt)
BLOCK
BOOLEAN
0
Block of function
ZREFSEL
INTEGER
1
Reference impedance selection
Table 137:
STTIPHIZ Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
START
BOOLEAN
Start
ALARM
BOOLEAN
Alarm
OPCIRC
BOOLEAN
Injection circuit open
ERROR
BOOLEAN
Error
ERRSTAT
INTEGER
Error indication
Table continues on next page
Section 7
1MRK502052-UEN B
Impedance protection
296
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...