Uinj
Rshunt
~
Step-up
Transformer
95 % SEF
10
0
%
S
E
F
REX060/SIM module
REG670
5
6
8
3
1
7
9
I
U
Generator
R
N
2
Generator Protection Panel
IEC11000067-2-en.vsd
U>
4
10
IEC11000067 V1 EN
Figure 133:
Example installation for stator injection
1
Generator unit consisting of a synchronous generator and a step-up transformer
2
Grounding resistor for the stator winding
3
Neutral point VT which is used as injection point and also to provide galvanic separation between
primary circuit and injection equipment
4
Cable used to inject the square-wave signal into the stator circuit
5
Connection for measurement of injected current. This signal is amplified in REX060 before it is
given to REG670 for evaluation.
6
Cable for measurement of injected voltage at the injection point. This signal is amplified in REX060
before it is given to REG670 for evaluation.
7
Two VT inputs into REG670 which are used to measure injected current and voltage
8
Cable for 95% stator earth-fault protection
9
Separate VT input in REG670 used for 95% stator earth-fault protection
10
Protection for excessive over-voltages posed by generator. REX060 can withstand without
damage maximum voltage of 120V and when used together with REX062 up to 240V.
Section 7
1MRK502052-UEN B
Impedance protection
300
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...