i1Mag
i2Mag
i3Mag
a==b
a
b
a==b
a
b
a==b
a
b
MAX
&
&
A
B
C
startPh1
startPh2
startPh3
&
&
&
start
³
1
IEC11000307_1_en.vsd
1
³
IEC11000307 V1 EN
Figure 151:
Logic diagram for the selection of the maximum current loop
The phase-to-earth voltage is compensated with zero sequence voltage in order to
avoid the function operating for earth faults in zone 1, that is, complete generator
stator winding and LV winding of the power transformer.
The reach settings for zone 2 can be provided using the
Z2Fwd
,
Z2Rev
and
ImpedanceAng
settings. The
Z2Fwd
is forward reach setting and
Z2Rev
is reverse
reach setting. The offset mho characteristic for phase-to-earth loop is shown in Figure
. The offset mho characteristics for phase-to-phase loop is shown in Figure
ß
1
2
IL Z Fwd
1
1
0
1
2
Ucomp
UL E U
IL Z Fwd
2
1
0
1
2
Ucomp
U L E U
IL Z REV
1
2
IL Z REV
1
IL jX
1
IL R
IEC11000299-2-en.vsd
IEC11000299 V2 EN
Figure 152:
Simplified offset mho characteristics for L1-to-E fault in zone 2
Section 7
1MRK502052-UEN B
Impedance protection
328
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...