IEC11000306-3-en.vsd
OpModeU< =
a<b
a
b
uP1P2
U<
a<b
a
b
uP2P3
U<
a<b
a
b
uP3P1
U<
1
Zone 3 Start
&
&
1
b0
b1
int
Zone 2 Start
10 ms
1
&
tU<
tPulse
= 1sec
TRUV
q
-1
STUV
Drop-Off
timer
0 =
Off
1 =
Z2Start
2 =
Z3Start
1
BLKUV
BLOCK
t
t
q
-1
IEC11000306 V3 EN
Figure 155:
Under voltage seal-in for zone 2 and zone 3
7.10.8
Technical data
Table 150:
ZGVPDIS Technical data
Function
Range or value
Accuracy
Number of zones
3
-
Forward reach
(3.0 - 200.0)% of Z
r
where Z
r
=UBase/√3∗IBase
±5.0% of set impedance
Conditions:
Voltage range: (0.1 - 1.1) x U
r
Current range: (0.5 - 30) x I
r
Reverse reach
(3.0 - 200.0)% of Z
r
where Z
r
=UBase/√3∗IBase
±5.0% of set impedance
Conditions:
Voltage range: (0.1 - 1.1) x U
r
Current range: (0.5 - 30) x I
r
Impedance angle
(5 - 90) degrees
-
Reset ratio
105% typically
-
Start time at 1.2 to 0.8 x set
impedance
Min. = 15 ms
-
Max. = 35 ms
Independent time delay to
operate at 1.2 to 0.8 x set
impedance
(0.000 – 60.000) s
±0.2% or ±40 ms whichever is
greater
Section 7
1MRK502052-UEN B
Impedance protection
332
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...