Section 8
Current protection
8.1
Instantaneous phase overcurrent protection 3-phase
output PHPIOC
8.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous phase overcurrent
protection 3-phase output
PHPIOC
3I>>
SYMBOL-Z V1 EN
50
8.1.2
Functionality
The instantaneous three phase overcurrent function has a low transient overreach and
short tripping time to allow use as a high set short-circuit protection function.
8.1.3
Function block
IEC04000391-2-en.vsd
PHPIOC
I3P*
BLOCK
ENMULT
TRIP
TRL1
TRL2
TRL3
IEC04000391 V2 EN
Figure 156:
PHPIOC function block
8.1.4
Signals
Table 151:
PHPIOC Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase current
BLOCK
BOOLEAN
0
Block of function
ENMULT
BOOLEAN
0
Enable current start value multiplier
1MRK502052-UEN B
Section 8
Current protection
333
Technical manual