8.4.7.5
Base quantities within the protection
The base quantities are entered as global settings for all functions in the IED. Base
current (
IBase
) shall be entered as rated phase current of the protected object in
primary amperes. Base voltage (
UBase
) shall be entered as rated phase-to-phase
voltage of the protected object in primary kV.
8.4.7.6
Internal earth-fault protection structure
The protection is internally divided into the following parts:
1. Four residual overcurrent steps.
2. Directional supervision element for residual overcurrent steps with integrated
directional comparison step for communication based earth-fault protection
schemes (permissive or blocking).
3. Second harmonic blocking element with additional feature for sealed-in blocking
during switching of parallel transformers.
4. Switch on to fault feature with integrated Under-Time logic for detection of
breaker problems during breaker opening or closing sequence.
Each part is described separately in the following sections.
8.4.7.7
Four residual overcurrent steps
Each overcurrent step uses operating quantity Iop (residual current) as measuring
quantity. Each of the four residual overcurrent steps has the following built-in
facilities:
•
Directional mode can be set to
Off
/
Non-directional
/
Forward
/
Reverse
. By this
parameter setting the directional mode of the step is selected. It shall be noted that
the directional decision (Forward/Reverse) is not made within the residual
overcurrent step itself. The direction of the fault is determined in common
“directional supervision element”.
•
Residual current start value.
•
Type of operating characteristic (inverse or definite time). By this parameter
setting it is possible to select inverse or definite time delay for the earth-fault
protection. Most of the standard IEC and ANSI inverse characteristics are
available. For the complete list of available inverse curves please refer to section
•
Type of reset characteristic (
Instantaneous
/
IEC Reset
/
ANSI Reset
). By this
parameter setting it is possible to select the reset characteristic of the step. For the
complete list of available reset curves please refer to section
""
.
1MRK502052-UEN B
Section 8
Current protection
365
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...