Table 222:
GOPPDOP Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
TRIP1
BOOLEAN
Trip of stage 1
TRIP2
BOOLEAN
Trip of stage 2
START
BOOLEAN
Common start
START1
BOOLEAN
Start of stage 1
START2
BOOLEAN
Start of stage 2
P
REAL
Active power P in MW
PPERCENT
REAL
Active power P in % of SBase
Q
REAL
Reactive power Q in MVAr
QPERCENT
REAL
Reactive power Q in % of SBase
8.11.5
Settings
Table 223:
GOPPDOP Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OpMode1
Off
OverPower
-
-
OverPower
Operation mode for stage 1 Off / On
Power1
0.0 - 500.0
%SB
0.1
120.0
Stage 1 overpower setting in Angle1
direction in % of SBase
Angle1
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for max power
senistivity stage 1
TripDelay1
0.01 - 6000.00
s
0.01
1.00
Trip delay for stage 1
DropDelay1
0.01 - 6000.00
s
0.01
0.06
Drop-off delay for stage 1
OpMode2
Off
OverPower
-
-
OverPower
Operation mode for stage 2 Off / On
Power2
0.0 - 500.0
%SB
0.1
120.0
Stage 2 overpower setting in Angle2
direction in % of SBase
Angle2
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for max power
senistivity stage 2
TripDelay2
0.01 - 6000.00
s
0.01
1.00
Trip delay for stage 2
DropDelay2
0.01 - 6000.00
s
0.01
0.06
Drop-off delay for stage 2
1MRK502052-UEN B
Section 8
Current protection
429
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...