Function
Range or value
Accuracy
Impulse margin time,
undervoltage
15 ms typically
-
Operate value,
overvoltage
(2-200)% of UBase
±0.5% of U
r
at U ≤ U
r
±0.5% of U at U > U
r
Definite time delay,
overcurrent, at 0 to 2 x
I
set
(0.000-60.000) s
±0.2% or ±35 ms whichever is
greater
Definite time delay,
undervoltage, at 1.2 x
U
set
to 0.8 x U
set
(0.000-60.000) s
±0.2% or ±35 ms whichever is
greater
Definite time delay,
overvoltage, at 0.8 x
U
set
to 1.2 x U
set
(0.000-60.000) s
±0.2% or ±35 ms whichever is
greater
8.14
Voltage-restrained time overcurrent protection
VRPVOC
8.14.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage-restrained time overcurrent
protection
VRPVOC
I>/U<
51V
8.14.2
Functionality
Voltage-restrained time overcurrent protection (VRPVOC) function can be used as
generator backup protection against short-circuits.
The overcurrent protection feature has a settable current level that can be used either
with definite time or inverse time characteristic. Additionally, it can be voltage
controlled/restrained.
One undervoltage step with definite time characteristic is also available within the
function in order to provide functionality for overcurrent protection with undervoltage
seal-in.
Section 8
1MRK502052-UEN B
Current protection
446
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...