8.14.3
Function block
VRPVOC
I3P*
U3P*
BLOCK
BLKOC
BLKUV
TRIP
TROC
TRUV
START
STOC
STUV
IEC12000184-1-en.vsd
IEC12000184 V1 EN
Figure 207:
VRPVOC function block
8.14.4
Signals
Table 241:
VRPVOC Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function both stages
BLKOC
BOOLEAN
0
Block of voltage restraint overcurrent stage (ANSI
51V)
BLKUV
BOOLEAN
0
Block of under voltage function
Table 242:
VRPVOC Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
TROC
BOOLEAN
Trip signal from voltage restrained overcurrent
stage
TRUV
BOOLEAN
Trip signal from undervoltage function
START
BOOLEAN
General start signal
STOC
BOOLEAN
Start signal from voltage restrained overcurrent
stage
STUV
BOOLEAN
Start signal from undervoltage function
1MRK502052-UEN B
Section 8
Current protection
447
Technical manual