Voltage
IDMT Voltage
Time
UL1
UL2
UL3
IEC12000186-1-en.vsd
IEC12000186 V1 EN
Figure 226:
Voltage used for the inverse time characteristic integration
Trip signal issuing requires that the undervoltage condition continues for at least the
user set time delay. This time delay is set by the parameter
t1
and
t2
for definite time
mode (DT) and by some special voltage level dependent time curves for the inverse
time mode (IDMT). If the start condition, with respect to the measured voltage ceases
during the delay time, and is not fulfilled again within a user defined reset time
(
tReset1
and
tReset2
for the definite time and
tIReset1
and
tIReset2
pickup for the
inverse time) the corresponding start output is reset. Here it should be noted that after
leaving the hysteresis area, the start condition must be fulfilled again and it is not
sufficient for the signal to only return back to the hysteresis area. Note that for the
undervoltage function the IDMT reset time is constant and does not depend on the
voltage fluctuations during the drop-off period. However, there are three ways to reset
the timer, either the timer is reset instantaneously, or the timer value is frozen during
the reset time, or the timer value is linearly decreased during the reset time. See
figure
and figure
Section 9
1MRK502052-UEN B
Voltage protection
484
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...