Time
Integrator
Voltage
Time
START
TRIP
START
U1>
START
TRIP
t
tIReset1
Time
t
Frozen Timer
Linearly
decreased
Instantaneous
Measured
Voltage
tIReset1
IEC05000020-3-en.vsd
HystAbs1
IEC05000020 V3 EN
Figure 244:
Voltage profile causing a reset of the START signal for step 1, and inverse time delay
Definite timer delay
When definite time delay is selected, the function will operate as shown in figure
Detailed information about individual stage reset/operation behavior is shown in
figure
and figure
respectively. Note that by setting
tResetn
=
0.0s
,
instantaneous reset of the definite time delayed stage is ensured.
Section 9
1MRK502052-UEN B
Voltage protection
512
Technical manual