en06000448.vsd
U
3N
U
3T
-
D
U
3
+
- U
3
+
- U
3N
+
+
U
3T,L1
-
+
U
3T,L2
-
+
U
3T,L3
-
IEC06000448 V2 EN
Figure 258:
Generator 3
rd
harmonic voltage characteristic at normal operation
The generator is modeled as parts of a winding where a 3
rd
harmonic voltage is
induced along the winding, represented by the end voltages U
3N
(voltage drop across
resistor) and U
3T
in the figure. Via the winding capacitances to earth and the neutral
point resistor there will be a small 3
rd
harmonic current, giving the voltages U
3N
and
U
3T
. The 3
rd
harmonic voltage in the generator neutral point (U
3N
) will be close to zero
in case of a stator earth-fault close to the neutral. This fact alone can be used as an
indication of stator earth-fault. To enable better sensitivity and stability also
measurement of the generator's 3
rd
harmonic voltage U
3T
is also used. In addition to
the decrease of U
3N
the generator voltage U
3T
will increase under the stator earth-fault
close to the generator neutral point. Therefore the 3
rd
harmonic voltage U
3T
, (which
is a zero sequence voltage) is used by the protection. In the 3
rd
harmonic voltage
differential protection algorithm equation
1MRK502052-UEN B
Section 9
Voltage protection
537
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...