Name
Values (Range)
Unit
Step
Default
Description
tResetDef_OV1
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for definite time
use of OV1
tResetIDMT_OV1
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for IDMT curves
for OV1
A_OV1
0.005 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for OV1
B_OV1
0.500 - 99.000
-
0.001
1.000
Parameter B for customer programmable
curve for OV1
C_OV1
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for OV1
D_OV1
0.000 - 10.000
-
0.001
0.000
Parameter D for customer programmable
curve for OV1
P_OV1
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for OV1
ResCrvType_OV2
Instantaneous
Frozen timer
Linearly decreased
-
-
Instantaneous
Selection of reset curve type for OV2
tResetDef_OV2
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for definite time
use of OV2
tResetIDMT_OV2
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for IDMT curves
for OV2
A_OV2
0.005 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for OV2
B_OV2
0.500 - 99.000
-
0.001
1.000
Parameter B for customer programmable
curve for OV2
C_OV2
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for OV2
D_OV2
0.000 - 10.000
-
0.001
0.000
Parameter D for customer programmable
curve for OV2
P_OV2
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for OV2
ResCrvType_UV1
Instantaneous
Frozen timer
Linearly decreased
-
-
Instantaneous
Selection of reset curve type for UV1
tResetDef_UV1
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for definite time
use of UV1
tResetIDMT_UV1
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for IDMT curves
for UV1
A_UV1
0.005 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for UV1
B_UV1
0.500 - 99.000
-
0.001
1.000
Parameter B for customer programmable
curve for UV1
C_UV1
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for UV1
D_UV1
0.000 - 10.000
-
0.001
0.000
Parameter D for customer programmable
curve for UV1
P_UV1
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for UV1
Table continues on next page
Section 11
1MRK502052-UEN B
Multipurpose protection
574
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...